Pressure Drop Calculations in Heat Exchangers
Pressure drop is a critical design parameter that affects pump/fan sizing, operating costs, and system performance. This guide covers calculation methods for various heat exchanger configurations.
Components of Pressure Drop
Total pressure drop consists of:
Single-Phase Tube-Side
Darcy-Weisbach Equation
ΔP = f × (L/D) × (ρV²/2)
Friction Factor Correlations
Laminar flow (Re < 2300):
f = 64/Re
Turbulent flow (Blasius):
f = 0.316 × Re^(-0.25) for Re < 10^5
Turbulent flow (Colebrook-White):
1/√f = -2log(ε/3.7D + 2.51/Re√f)
Typical Design Values
Two-Phase Pressure Drop
Homogeneous Model
Treats mixture as single fluid with average properties:
ΔP_tp = f_tp × (L/D) × (G²/2ρ_m)
Separated Flow Model (Lockhart-Martinelli)
ΔP_tp = ΔP_l × φ_l²
Where φ_l is the two-phase multiplier based on Martinelli parameter X.
Friedel Correlation
More accurate for refrigerants:
φ_lo² = E + 3.24FH / (Fr^0.045 × We^0.035)
Air-Side Pressure Drop
Plain Fins
ΔP = f × (A_o/A_c) × (ρV_max²/2)
Wavy/Louvered Fins
Use appropriate friction factor correlations from literature.
Typical Design Values
Shell-Side Pressure Drop
Bell-Delaware Method
Accounts for:
ΔP_s = ΔP_c × R_b × R_l + ΔP_w × N_b
Kern Method (Simplified)
ΔP_s = f × G_s² × D_s × (N_b + 1) / (2ρ × D_e × φ_s)
Minor Losses
K-Factor Method
ΔP = K × (ρV²/2)
Typical K values:
Equivalent Length Method
Convert fittings to equivalent pipe length:
L_eq = K × D / f
Design Considerations
Allowable Pressure Drops
ApplicationTube-sideShell/Air-side
Water systems35-70 kPa20-50 kPa
Refrigerant20-50 kPa30-100 Pa
Process fluids10-100 kPaVaries
Trade-offs
Conclusion
Accurate pressure drop calculations ensure proper system design and efficient operation. Consider all components and use appropriate correlations for the specific application.